Skip to content

Irrigation Reduced Pressure Backflow Assembly

March 3, 2015

Wilkins 975XL RPBA installed below groundI have just restored service for this improperly installed irrigation backflow assembly. This is a 1″ Wilkins 975XL RPBA which is installed below ground with no daylight drain. When this backflow assembly fails the box may fill with water and create a potential indirect crossconnection.

As a backflow assembly tester it is important  to note this on your test report  to relieve yourself of any liability.        Click photo to enlarge

Improper New Installations

January 18, 2015

Improper DCVA InstallsThe photo on the right is a good example of some of the improper new installations we run across from time to time.

Backflow preventer’s are required  t0 have 12″  of clearance below the assembly.  These look like they were installed  then covered up with dirt to set the boxes.

4” Ames 2000SS Check Valve Failure

December 12, 2014

WP_Ames 2000SS Cam Check_ProThis is a Cam Check out of a 4″ Ames 2000SS, the area circled in yellow is typical of what you will find when these assemblies fail.

These rubber parts are not replaceable and this cam check had to be replaced.

click on photo to enlarge

 

Unapproved Backflow Assembly Modification

October 18, 2014

Improper installation at a tanker fill station ILLPhoto compliments of Redwood Backflow, Redmond Washington. 

This is an unapproved modification to a backflow assembly for a commercial tanker fill station.

The equipment circled in this photograph should have been installed downstream of shutoff valve #2 where the arrow is pointing. Currently the device is installed between test cock #3 and test cock #4.

This backflow assembly failed the backflow test; however there is no way of knowing if this assembly is failing because of a bad check valve,  or as a result of the unapproved improper installation. The backflow assembly must be disassembled and reassembled properly before an accurate backflow test can be made.

As a certified backflow assembly tester you must mark this as an improper installation and explain why in the remarks section on your test report. You are required to “inspect” as well as “test” the assembly. Your test report is a legal document, when filled out properly it will protect you from liability.

Factory Defective Backflow Assemblies

October 5, 2014

Factory defective seat on a 4 inch Febco 870The ballpoint pen in this picture is pointing at a casting defect on the bottom of a 4″Febco 870 seat.

This defect is prohibiting the seat from coming into full contact with the seat gasket and the assembly to provide a watertight seal.

When inspecting parts during a repair, it is important to take the time to inspect the entire part not just one side for damage, manufacturing defects, etc.

Click photo  to enlarge

Backyard Backflow Assembly Mechanic

August 16, 2014

WP_009M2QT _ProThis is a 1″ Watts 009M2QT relief valve. It was tested by a certified backflow tester when it was installed and  it passed the initial test.

Some time after that and prior to the home being sold the assembly began to vent water. Most likely the builder, in his infinite wisdom, had a carpenter fix it. The odds are the technician damaged the piston O-ring upon reassembly causing water to flow through the relief valve stem vent. The technician rectified the problem by plugging the relief valve stem vent with a screw. The technician also failed to reinstall the relief valve spring. As a result he succeeded in making sure the relief valve would never open again.

This is just one reason why we test  the backflow assemblies annually.  Aside from failures due to normal wear and tear,  there are folks out there who think  they are doing the right thing  by modifying an assembly  in an attempt to repair it.  These modifications reduced a high hazard protection backflow assembly,  to a low hazard device, and of course this is not allowed.

Mixed Up Backflow Detector Assembly

September 27, 2013

8” Colt 300BF

This is a new installation of an 8” Colt 300BF with a ¾” Ames 2000BM3 detector assembly.

If you look closely you will see the upstream side of the ¾” Ames 2000BM3 is connected to shut off valve #2, and the downstream side is connected to shut off valve #1. The detector meter itself is connected correctly with the direction of flow arrow pointing up. However with the way this is set up the detector meter can only run backwards.

This is an improper installation which has created an unprotected cross connection.

Click photo to enlarge

.

Follow

Get every new post delivered to your Inbox.

%d bloggers like this: